Max No. of Zones   20
Max No. of Devices   999
Max No. of Panels per System   5
Wired Sounder Circuits
(Output)
  2 x 24v 0.5A
Selectable Continuous/Pulsed
 Alarm Indicators   Twin Flashing Red LEDs
Addressable Fire Message on LCD indicating Unit number, Device type, and Zone number
Fault Indicators   Amber LED
LCD indicating unit number and fault type
Event Log   300 events
Supply   Mains: 230V 50Hz 75VA max
Battery:
12V 7.2Ah sealed lead acid giving 72 hour standby
External DC   24V 3.5A max
Outputs   24V 0.5A
Auxiliary Relays   1A changeover contacts
Inputs   Wired call point monitored circuit, 4k7 ohm end of line resistor monitored for open & short circuit
Operating Frequency   173.225 MHz
Modulation     NBFM
Output Power (ERP)   10mW
Operational Temperature   0 to +60C
Applicable Standards & Approvals:
European Fire Alarm
British Standards
R&TTE
EMC Standard

Electrical Safety
 
EN54-2 and 4
BS5839 Part 1:2002
EN300 220
EN301 489-3
EN50130-4
EN60950:2001